tk8000-尊龙登录



tk8000-ex thermocouple isolated barrier

http://www.ahdqjt.com     time: 11/26/10 15:48

general description
tk8000-ex thermocouple isolated barrier or temperature transmitter, converts thermoelectric power from the thermocouple to 4 ~ 20madc (or 1 ~ 5v dc) output, which has a linear relationship with temperature. so it has automatic cold junction compensation function.

main technical parameters
explosion-proof marker:[exia]ⅱc
power consumption: about 1.5w(24v power supply, when the output is 20ma)
the danger zone input:
signal types: thermocouple signal j, k, t, e, s, b and mv signals
signal range:0~60mv
measuring range: 20 ~ 60mv (according to customer orders)
the safety zone output:
tk8000-ex,tk8000-ex(v)
signal:4~20ma ,1~5v
output load:100~500ω,250ω(internal)
output accuracy:0.2% f.s
cold junction compensation accuracy:1/20℃
(compensation range:0~50℃)
temperature drift:0.01% f.s/℃
continuous operating temperature: 0~+50℃
certified by china national quality supervision and test center for explosion protected  electrical products(cqst) (between terminals 9 and 10)
u0≤4v,io≤90ma,co≤100μf,
lo≤ 4.2mh,po≤0.9w
applying to field devices
0.02mh, thermocouple signal j, k, t, e, s, b, mv signal sensor.
instrument selection


type

input signal

output signal

channels

tk8061-ex

e,k,s,b,r,t,j

4~20ma /1~5v dc

single

tk8069-ex

e,k,s,b,r,t,j

4~20ma /1~5v dc

one entrance, two exit  