butadiene pvc compound soft cable

http://www.ahdqjt.com     time: 11/10/10 10:33

   it is used for supervising and controlling return circuit of a.c. rated voltage of 450/750v or lower, power connection of various mobile electrical equipments, radio devices, and lighting & protection under low temperature.

executive standard: enterprise standard and jb1170-75 standard

working condition

  1. long-term working temperature of wire conductor is no more than 180℃ for cable with silicon insulation, 70℃ for that with pvc insulation
  2. min. environment temperature of wire is -40℃
  3. bending radius allowed by wire is no less than 8 times that of cable o.d or 6 times for cable with soft structure.

type and description


type

cable description

note

yvfr

soft power cable with cu core, butadiene pvc insulation and sheath

if thin-plated copper wire braided shielding is needed, the letter “p” in the original type of cable shall be changed into the letter “p1”.
if thinned copper wire conductor is used, the relevant description shall be made in the order, but it is not necessary to give other description in cable type

 

 

yvfb

flat type soft power cable with cu core, butadiene pvc insulation and sheath

ygvfb

flat type soft power cable with cu core, silicon rubber insulation and butadiene pvc sheath

kvfr

soft control cable with cu core, butadiene pvc insulation and sheath

kvfrp

soft control cable with cu core, butadiene pvc insulation and sheath, copper wire braided shielding

kvfb

flat type soft control cable with cu core, butadiene pvc insulation and sheath

kgvfb

flat type soft control cable with cu core, silicon rubber insulation and butadiene pvc sheath

main technical parameter

  1. max. dc resistance of conductor at 20℃ shall meet the requirement of the following table

nominal cross section area (mm2)

conductor structure
pieces/diameter (mm)

conductor dc resistance at 20℃≤ω/km

not tinned

tinned

0.5

16/0.20

39.0

40.1

0.75

24/0.20

26.0

26.7

1.0

32/0.20

19.5

20.0

1.5

30/0.25

13.3

13.7

2.5

49/0.26

7.98

8.21

4

56/0.30

4.95

5.09

6

84/0.30

3.30

3.39

10

84/0.40

1.91

1.95

16

110/0.43

1.21

1.24

25

170/0.43

0.78

0.795

35

240/0.43

0.554

0.565

50

342/0.43

0.386

0.393

70

482/0.43

0.272

0.277

95

654/0.43

0.206

0.210

120

827/0.43

0.161

0.164

150

1033/0.43

0.129

0.132

185

1274/0.43

0.106

0.108

    • finished control cable shall bear a.c. test voltage of 3000v under power frequency for 5 min without puncture of insulation
    • finished power cable shall bear a.c. test voltage of 3500v under power frequency for without puncture of insulation