it is used to transmit and distribute power of a.c rated voltage 0.6/1 kv or lower for power system. it has not only better performance of pvc insulation power cable, but also advantages of softness and flexibility as well
executive standard: yd/t1173-2001
type and description:
type |
description |
rv |
soft power cable with cu core, pvc insulation |
rvz |
soft power cable with cu core, pvc insulation, flame resistant |
rvv |
soft power cable with cu core, pvc insulation and sheath |
rvvz |
soft power cable with cu core, pvc insulation & sheath, flame resistant |
rvv22 |
soft power cable with cu core, pvc insulation & sheath, steel tape armor |
rvvz22 |
soft power cable with cu core, pvc insulation & sheath, steel tape armor, flame resistant. |
production condition
- max. temperature of cable conductor for long-term working is 70℃
- min. environment temperature for installing cable is 0℃
- bending radium allowed by cable:
it will be no less than 8 times that of cable o.d for inarmored cable and 20 times that of cable o.d for armored cable
- max. working temperature of cable conductor is 160℃ during short circuit (the longest lasting time shall be no more than 5 seconds).
main technical parameter
- max. dc resistance value of conductor at 20℃ shall meet the requirements of the following table:
nominal cross section area |
1.5 |
2.5 |
4 |
6 |
10 |
16 |
25 |
35 |
50 |
max. dc resistance of conductor at 20℃ |
13.3 |
7.98 |
4.91 |
3.30 |
1.91 |
1.21 |
0.780 |
0.554 |
0.389 |
nominal cross section area |
70 |
95 |
120 |
150 |
185 |
240 |
300 |
400 |
|
max. dc resistance of conductor at 20℃ |
0.272 |
0.206 |
0.161 |
0.129 |
0.106 |
0.0801 |
0.0641 |
0.0495 |
|
- min. insulation resistance at 70℃
nominal cross section area (mm2) |
min. insulation resistance at 70℃ |
nominal cross section area |
min. insulation resistance at 70℃ |
1.5 |
0.01. |
70 |
0.0032 |
2.5 |
0.009 |
95 |
0.0032 |
4 |
0.007 |
120 |
0.0029 |
6 |
0.006 |
150 |
0.0029 |
10 |
0.0056 |
185 |
0.0029 |
16 |
0.0046 |
240 |
0.0028 |
25 |
0.0044 |
300 |
0.0028 |
35 |
0.0036 |
400 |
0.0026 |
50 |
0.0037 |
/ |
/ |
testing condition:
|
- a.c. voltage test under power frequency
the finished cable shall bear a.c. voltage test of 50hz listed in the following table without puncture
core no. |
testing method |
sample length |
voltage |
lasting time |
|
rated voltage |
testing voltage |
5min |
|||
single core |
immersing in the water for 1th |
manufacturing length |
450/750 |
2500 |
|
multi-core and armoring |
interphase |
600/1000 |
3500 |
cables